Possible Reasons for Low COP
(1) Fouling of Evaporative Condenser Tube
Water temp is high (26 to 34°C), compared to wet bulb temp (20°C). Generally water temp is wet bulb temp plus at most 5°C. It suggests condenser tube fouling. Proper maintenance of condenser and water quality control are necessary.
(2) Performance of pool evaporator seems to be degraded
(3) Flow pattern of ice water in the pool is not optimum
(4) Compressor performance seems to be degraded
due to aging

Canned Food Factory Proposals & Potential Saving
Proposals Saving (US$/yr)
Housekeeping of condenser & evaporator
(oil purge, non-condensing gas, defrosting)
58,700
Modernization of refrigeration system(1)
(rearrangement of compressors, pump-circulation type evaporator, etc)
152,000
Modernization of refrigeration system(2)
(evaporative condenser)
76,000
Repair of insulation in cold storage rooms 48,600
Automatic control of auxiliary facilities 21,000
Total 356,300