  • Buildings having a total floor area of 2,000 m2 or less
  • No regulations

<4> Standards of specifications of lighting fixtures

  • Buildings having a total floor area of 2,000-5,000 m2
  • For lighting fixtures installed in buildings having a total floor area of 5,000 square meters or less, the score, which is calculated by adding 80 to the total of the evaluation scores listed in (1) to (3) below, shall be 100 or more.

    Evaluation items are shown in (1) to (3) below. The value obtained by adding 80 to the total is required to be 100 or more as the judgement criteria.

    (1) The evaluation score for the lighting efficiency of lighting fixtures (Table 3.17)
    (2) The evaluation score for the control method of lighting fixtures (Table 3.18)
    (3) The evaluation score for the layouts of lighting fixtures and setting of
        illuminance. (Table 3.19)

        The score is evalulated as follows: 

             Point = 80 + ((1) + (2) + (3))

Table 3.17 The evaluation score of the lighting fixtures

Table 3.18 The evaluation control method of lighting fixtures score of the lighting fixtures